Settings
37
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Name
Range
Default
Description
Close =
Warning
+
Open =
Warning
+
Close =
Failure
+
Open =
Failure
+
- VDO R/0-180 supports a VDO fuel level sensor of the range 0 Ohms to 180
Ohms
DAT R33-240 and VDO R/0-180 can not be used on port A. To use on port A
store as a custom sender table using the RapidCore Configuration software.
**A custom table created using the RapidCore Configuration Software. The
text (custom sender) will be replaced with the custom text you choose when
creating the sender.
+
The switch must close to ground.
Trim Offset
-50.0 ~
50.0%
0.0 %
Calibrate a sensor by using the offset to correct errors. Only applies if Sensor
Type has been set to a sender.
Setpoints ->
Bypass Time
0 ~ 90
seconds
30 s
Amount of time to bypass warnings and failures after engine has started.
Setpoints >
Low Warning
Disabled,
1 ~ 90%
25 %
Reading at which a "Low Fuel Level" warning occurs. Only applies if Sensor
Type has been set to a sender. Only monitored in the RUN mode.
Setpoints >
Low Failure
Disabled,
1 ~ 90%
5 %
Reading at which a "Low Fuel Level" failure occurs. Only applies if Sensor
Type has been set to a sender. Only monitored in the RUN mode.
Setpoints >
High Warning
Disabled,
1 ~ 125%
Disabled
Reading at which a "High Fuel Level" warning occurs. Displays 'High Fuel
Level' on the screen. Only applies if Sensor Type has been set to a sender.
Monitored globally including OFF and AUTO.
4.4.4
Engine Speed
Use the following settings' configurations to allow the controller to read and interpret speed sensing data.
Name
Range
Default
Description
Signal Source
J1939 Bus
Mag Pickup
Genset Voltage
Genset
Voltage
The source for the engine speed signal.
J1939
-- Engine speed is obtained over the engine CAN
communication bus .
Genset Voltage
-- The AC Voltage connector phase A is used for
engine speed.
Mag Pickup
-- A magnetic pickup, alternator output, or the distributer
signal can be used to sense speed. Must use J6 pins 7 and 8. If using
a distributer a filter is often required. Contact DYNAGEN for more
information on using a distributer signal.
Speed Settings > Rated
RPM
500 ~ 4000 rpm
in 1 rpm
increments
1800
rpm
Speed at which the engine runs under normal operating conditions.
Warning and failure setpoints are calculated from this setting.
Speed Settings > Idle
RPM
300 ~ 2000 rpm
in 1 rpm
increments
900 rpm
Speed at which the engine runs when it is idling.
Speed Settings > Tooth
Count
1 ~ 600
110
(only applies when Signal Source is set to Mag Pickup) Number of
teeth on the flywheel.
If the number of teeth is unknown the following formula can be used.
A multimeter must be used to measure the AC frequency (Frequency-
In-Hz below) from the magnetic pickup. The speed (Speed-In-Rpm
below) must be known.
Tooth-Count = (Frequency-In-Hz * 60) / Speed-In-Rpm
Setpoints > Low Warn
(Under Speed Warning)
20 ~ 99%
90 %
Reading at which a warning occurs.
Setpoints > Low Fail
(Under Speed Failure)
20 ~ 99%
85 %
Reading at which a failure occurs.
Setpoints > High Warn
(Over Speed Warning)
101 ~ 150%
110 %
Reading at which a warning occurs.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...