Settings
47
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
4.4.6.2 Start on Low Example
In this example, a sensor is monitoring the voltage of an external battery bank. If the voltage falls below 10.5V, the engine will
start and run for 40 minutes to charge the battery.
Relevant Settings
Setting
Value
Signal Source
Sensor Port X
Display
Enable
Sensor Type
Custom
Sensor Table Name
Battery Bank
Active Range
N/A (These ranges are fixed for Start on Low / High)
Mode Select
Start on Low
Mode Settings -> Active Time
40 minutes
Mode Settings -> Start Level
10.5V
Mode Settings -> Stop Level
1
Disabled
1
Stop Level needs to be disabled when the engine is running because the battery voltage will equal the alternator charging
voltage. Having this disabled will force the engine to run for the entire duration of the active time.
The chart above shows the connection between a battery bank and time. At approximately 80 minutes time, the voltage falls
below the 10.5V start threshold causing the engine to start. The engine runs for the 40 minutes active time regardless of the
voltage reading and then shuts down.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...