Settings
28
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
4.2
Switched Inputs
The controller has five switched inputs which cause the controller to perform a function when activated.
Default settings:
Switched Input Default Value
Switched Input
A
Emergency Stop
Switched Input
B
Start / Stop
Switched Input
C
Disable
Switched Input
D
Disable
Switched Input
E
Disable
Switched I/O > Switched IN X:
Name
Range
Description
Function
[Menu] See below.
The function that the switched input performs when active.
Active Mode
[Menu] See below.
Determines the operating conditions under which the switched input can
be active. Multiple selections are allowed.
Trigger
[Menu] See below.
The state of the input determining if it is active or inactive.
Switched I/O > Switched IN X > Function:
Name
Active Mode
Description
Disabled
N/A
Input is disabled and has no function.
Start / Stop
Auto, Running
Starts the engine when active, stops the engine when deactivated. It is
recommended to set the Trigger mode to Close +BAT for better noise
tolerance.
If Trigger mode is set to "Open" or "Close +BAT/GND" the start/stop input
will act like a momentary input. A pulse of 2 to 4 seconds will start
controller. Another pulse of 2 to 4 second duration is required to stop the
controller. If the input is just turned off, the controller will continue to run.
Emergency Stop
Global
When active, shuts down the engine, displays Emergency Stop, and
prevents leaving the OFF mode.
CAUTION !!! This should only be used for emergency stop indication on
the controller. The installer must provide an independent means to shut
down the engine from the emergency stop button such as cutting off fuel.
See the typical wiring diagrams for an example on how to wire up the
emergency stop.
Idle Mode
Running
section under Engine Logic for more information.
Voltage Select 1
Auto
Used for changing the system AC voltage configuration. See
Voltage Select 2
Auto
Charger Fault (Battery
Charger Fault)
Global
Controller displays 'Charger Fault' warning when active.
Mom. Start (Momentary
Start)
Auto
Starts or stops the engine when momentarily active for at least 2
seconds.These inputs
allow the user to wire separate inputs for start and
stop or to use a push button instead of a toggle switch.
Momentary stop will only stop the controller when the reason for start was
"momentary start". It will not stop if the front panel run button was used to
start the engine.
Mom. Stop (Momentary
Stop)
Running
Configurable Warning 1 Configurable
Controller displays a warning or failure with configurable text* when active.
In the case of the configurable failures a shutdown is also performed.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...