Settings
53
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
4.5.1.4 Idle
Controller ignores under speed, voltage and frequency warnings and failures when active. If using J1939, the controller will
broadcast TSC1 as the Idle Speed parameter found in the
section.
This section explains the general idle functionality.
There are three ways to use idle:
1.
Warmup Idle -- Automatically enter the idle mode during warmup for a period of time before going to rated speed. See
.
2.
Cool down Idle -- Idle automatically during cool down. See below.
3.
Idle Switched Input -- Idle whenever this switched input is active. See the Idle Mode function under
Name
Parent Menu
Range
Default
Description
Warmup
Idle
Timers > Engine
Logic
Disable
Warm-up
Timer
Oil Temp.
Engine Temp.
Refer to the
Idle
Settings
Timers > Engine
Logic
[Menu]
Cooldown
Idle
Timers > Engine
Logic
Disable
Enable
Disable
Idle during cooldown.
Auto Idle
Link
Timers > Engine
Logic
Disable,
Breaker Trip
Disable
If set to breaker trip, the breaker trip will be activated
whenever the controller is in the Idle mode. The breaker trip
will be turned off when Idle mode is exited if it was not in the
latched state.
If the user delaches the breaker trip output while auto idle is
active the breaker trip will turn off for one second and then
turn back on.
Idle Switched Output
A switched output can be set to Idle to turn on whenever Idle mode is entered. This is useful for electronic governors that have
an idle input to tell the governor to run the engine at idle speed. Note that the switched outputs are meant to drive relays so a
relay must be installed to do the logic to the governor.
4.5.1.4.1 Warmup Idle
This section explains the Warmup Idle functionality.
The warmup idle is used to run the engine at a reduced speed at engine start.
Name
Parent Menu
Range
Defaults
Description
Warm-
up Idle
Timers > Engine
Logic
Disable
Warm-up
Timer
Oil Temp.
Engine
Temp.
Disable
If enabled the engine is placed in Idle mode during the warm-up period.
Warm-up Timer -- The engine idles during the duration of the warm-up
timer countdown.
Oil Temp. -- The oil temperature over J1939 is used to determine the
extent of the warm-up / Idle period.
Engine Temp. -- Same as Oil Temp. but the engine temperature is
used. The engine temperature can come locally or from J1939.
The oil temp and engine temp selections use the Debounce, Low Point,
and High Point settings below.
Debou
nce
Timers > Engine
Logic > Idle
Settings
1 to 10 s,
1s
increments
10 s
(Warm-up Idle) If the temperature remains between the "Low Point"
and "High Point" settings for this time exit the warm-up / idle.
Low
Point
Timers > Engine
Logic > Idle
Settings
1 to 180
0
F,
1
0
F
increments
32 F
(Warm-up Idle) Continue to idle when the temperature is below this
setting. Ignore the Debouce.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...