Settings
58
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Name
Range
Default
Description
Setpoints >
High Warn
101 ~ 150 % in 1 %
increments
110 %
Reading at which a warning occurs.
Setpoints >
High Fail
101 ~ 150 % in 1 %
increments
115 %
Reading at which a failure occurs.
*NOTE
: 800 VAC applies to software logic only. Do not exceed 600 VAC on the AC Voltage terminals including
during over voltage warning and failure conditions.
Application Note: Scaling Factor
The scaling factor setting can be used to calibrate the AC voltage if there are discrepancies between the reading and the actual
value. It can also be used if transformers are used to step up / down the voltage. The scaling factor applies to all phases in a
system.
Example: The voltage source is a 3-Wire 3-Phase system with a nominal voltage of 208 VAC. The controller is reading 206.3
VAC but a calibrated multimeter gives 208.3 VAC. Use the formula below to determine the scaling factor.
1.
Scaling Factor = Multimeter Reading / Controller Reading
2.
Scaling Factor = 208.4 VAC / 206.3 VAC
3.
Scaling Factor = 1.010
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...