Settings
29
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Name
Active Mode
Description
The RapidCore Configuration Software must be used to change the text.
The settings under Timers > Trigger Delays > Config Inputs and Timers >
Trigger Delays > Config Fail 3 can be set to control the amount of time the
input has to be active to trigger.
Configurable Warning 2 Configurable
Configurable Failure 1
Configurable
Configurable Failure 2
Configurable
Configurable Failure 3
Configurable
Air Press. Fail (Air
Pressure Failure)
Cranking
Controller displays 'Low Air Pressure' and shuts down engine when active.
Hyd Pres. Fail (Low
Hydraulic Pressure
Failure)
Cranking
Controller displays 'Hydraulic Pressure Failure' and shuts down engine
when active.
Oil Pres Warn (Low Oil
Pressure Warning)
Running
Controller displays 'Oil Pressure Warning' when active.
Cool. Lvl Fail (Low
Coolant Level Failure)
Global
Controller displays 'Low Coolant Lvl' and shuts down engine when active.
High Fuel Warning
Global
Controller displays 'High Fuel Level' warning when active.
Lamp Test
Global
Controller performs lamp test when active. If the controller is in the
FAILURE mode the LED will remain red. The only indication that the lamp
test is active is the LED indicator will alternate between the green and red
colors. The LED goes back to it's original state when the switched input is
no longer active.
Fuel In Basin
Global
Controller displays 'Fuel In Basin' warning when active.
Battle Mode
After Cranking
Controller ignores all warnings and failures when active. Displays 'Battle
Running' when active. If a failure occurs during Battle Mode it is 'latched'
and the engine will shutdown on failure when the controller leaves Battle
Mode.
Start Inhibit
Global
Controller ignores all start commands and the engine cannot start when
active. Once Start Inhibit becomes inactive, starting is enabled again. If
the engine is running, activating this input will shut down the engine and
place the controller in AUTO mode.
RPM Switch (Primary
RPM / 60Hz -
Secondary RPM / 50Hz
Select)
Auto
Used for changing between Primary and Secondary RPM for an engine or
50Hz / 60Hz for a generator. See
information.
ECM Preheat (ECM
Preheat Signal)
Cranking (during the
Preheat countdown
only)
Controls preheating using a switched input. See Switched Input in the
Remote Reset
Global
Allows the controller to be reset from a failure mode.
- Momentary action for 3 - 5s in FAILURE mode will place the controller in
OFF mode.
- Momentary action for 3 - 5s in OFF mode will place the controller in
AUTO mode.
- Momentary action for 3 - 5s in RUN mode will place the controller in
AUTO mode. Cool-down is skipped.
NOTE
: More than one Active Mode can be selected.
The active modes is only configurable if the Function menu is set to one of the configurable switched input functions.
It is fixed for all other functions.
Switched I/O > Switched IN X > Trigger:
Name
Description
Close +BAT
Input is active when +Battery is present at the terminal.
Close GND
Input is active when Ground is present at the terminal
Close +BAT/GND
Input is active when Battery or Ground is present at the terminal.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...