Settings
33
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Name
Active Mode
Description
Breaker Trip
Running
Output is controlled by the Over Current Failure, IDMT and Load
Imbalance features. The breaker Trip only reacts to over current faults; It
does not activate for other failures.
Auto Idle
Warm-up, Cooldown
Active at the start of delay to start until the end of warm-up if warmup idle
is enabled. Also active during cooldown if cooldown idle is enabled. See
Warm-up Idle and Cooldown Idle in
. This output does not
react to the Idle switched input.
Rpm Output
Running
Refer to the
feature under Sensors > Engine Speed for more
information.
Amb Temp Out
Running
Used by the J1939 Ambient Air Temperature Control feature. Refer to the
J1939 Reference manual for more details.
Warning Functions
Functions
Low Engine Temperature
High Engine Temperature
Low Oil Pressure
Under Speed
Over Speed
Low Fuel Level
High Fuel Level
Low Battery Voltage
High Battery Voltage
Under Frequency
Over Frequency
AC Under Voltage
AC Over Voltage
Over Current
Fuel In Basin
Battery Charger Fault
Configurable Warning 1
Configurable Warning 2
Auxiliary Sensor 1
Auxiliary Sensor 2
Auxiliary Sensor 3
Auxiliary Sensor 4
Name
Active Mode
Description
Load Imbalance
Running
AC current phases do not match. (More Information)
DTC Received. (DTC/MIL)
Running
Active when controller receives a DM1 from the ECM.
Failure Functions
Functions
Overcrank
Engine Failed to Stop
DM1 Stop Lamp
High Engine Temperature
Low Oil Pressure
Low Fuel Level
Under Speed
Over Speed
Low Battery Voltage
High Battery Voltage
Low Coolant Level
Low Air Pressure
Low Hydraulic Pressure
Under Frequency
Over Frequency
AC Under Voltage
AC Over Voltage
Over Current (TG410 only)
ECM Communication Failure
Configurable Failure 1
Configurable Failure 2
Config Fail 3
Auxiliary Sensor 1
Auxiliary Sensor 2
Auxiliary Sensor 3
Auxiliary Sensor 4
---
Name
Active Mode
Description
Load Imbalance
Running
AC current phases do not match. (More Information)
Exception Fault*
All
When the controller encounters an unhandled exception or
lockup (watchdog triggered) it will reset and enter the failure
mode as an exception fault.
*The name of this fault is configurable form the Configuration
Software.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...