Using the Controller
24
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Sensor 2
Run
Event
The controller has auto started due to a auxiliary sensor 2 "start on low" or "start on high" request.
Sensor 1
Stop
Event
The controller has shutdown due to a auxiliary sensor 1 "start on low" or "start on high" stop request.
Sensor 2
Stop
Event
The controller has shutdown due to a auxiliary sensor 2 "start on low" or "start on high" stop request.
Switch
Start
Event
A controller start was triggered by the momentary start switched input.
Switch
Stop
Event
A controller start was triggered by the momentary start switched input.
Regen
Inhibited
Event
Electronic engines with a Diesel Particulate Filter (DPF) only. The user requested that the automatic
regeneration of the DPF be disabled.
Force
Regen
Event
Electronic engines with a Diesel Particulate Filter (DPF) only. The user requested a manual
regeneration of the DPF.
Auto
Regen
Event
Electronic engines with a Diesel Particulate Filter (DPF) only. The engine ECM has performed an
automatic regeneration of the DPF.
Sensor 3
Run
Event
The controller has auto started due to a auxiliary sensor 3 "start on low" or "start on high" request.
Sensor 4
Run
Event
The controller has auto started due to a auxiliary sensor 4 "start on low" or "start on high" request.
Sensor 3
Stop
Event
The controller has shutdown due to a auxiliary sensor 3 "start on low" or "start on high" stop request.
Sensor 4
Stop
Event
The controller has shutdown due to a auxiliary sensor 4 "start on low" or "start on high" stop request.
Log Time
start
Event
A user has started the controller using the RUN button and the long time run feature is enabled under
Timers > Long Time Run. The controller will run for the duration specified under "Long Time Run"
and then automatically shut down.
Scheduler
Start
Event
The controller has auto started due to a daily schedule set up in Timers > Week Scheduler.
Start
Canceled
Event
A daily scheduler was canceled either because the controller was not in AUTO mode or start request
was ignored. A start request being ignored is an internal error and should not occur.
J1939 Start Event
Controller started from J1939 using the second J1939 start/stop method. Refer to the J1939 user
guide for more information. This is often used by telemetry devices to start/stop the controller.
Crank
Failed
Warning
The controller has turned it's crank output but has failed to detect the engine is running. After crank
rest (if programmed under Timers > Engine Logic) it will try again.
Low Batt
InCrank
Warning
During cranking the battery was lower than normal. The level is set under Sensors > Battery.
Charger
Fault
Warning
Indicates a battery charger issue. The controller has a battery charger fault switched input. This is
used to indicate to the controller the charger has a fault.
High Fuel
Level
Warning
The fuel level raised above the high fuel level warning threshold set under Sensors > Fuel Level.
Potential over fueling issue.
Under
Voltage
Warning
The generator AC voltage has fallen below the under voltage warning setpoint set under AC Monitor
> Genset Voltage. Possible issue with the voltage regulator or governing on the engine.
Under
Speed
Warning
The generator speed has fallen below the under speed warning setpoint set under Sensors > Engine
Speed.
Over
Speed
Warning
The generator speed has risen above the over speed warning setpoint set under Sensors > Engine
Speed.
High
Engine
Temp
Warning
The engine temperature has risen above the high engine temperature warning under Sensors >
Engine Temp.
Low Oil
Pressure
Warning
The oil pressure has fallen below the low oil pressure warning setpoint under Sensor > Oil Pressure.
Low Fuel
Level
Warning
The fuel level has fallen below the low fuel level warning setpoint under Sensors > Fuel Level.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...