Using the Controller
23
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Event
Name
Event
Type
Description
Power On
Event
The controller has powered on.
Auto
Enabled
Event
The controller has entered AUTO mode. The controller is waiting for a manual or automatic start
condition such as a remote/start stop command.
Off
Enabled
Event
The controller has entered OFF mode (Not in Auto displayed on screen). Automatic starting is
disabled.
Manual
Start
Event
A user has pressed the RUN button on the controller.
Start
Cooldown
Event
The controller has entered cooldown. Cooldown has to be enabled under Timers > Engine Logic.
Remote
Start
Event
A switched input remote start has been triggered. The controller will start.
Remote
Stop
Event
A switched input remote stop has been triggered. The controller will stop.
Emergency
Stop
Event
The switched input Emergency Stop has been triggered. The controller has performed an emergency
shutdown skipping cooldown.
Start
Charging
Event
The controller has auto started because of a low starter battery condition. The low battery restart has
to be enabled under Sensors > Battery.
Stop
Charging
Event
The controller has ran for the programmed amount of time to recharge the starter battery and is
shutting down.
Service
Required
Event
The controller requires maintenance. This has to be enabled under Timers > Maintenance. Also after
maintenance is performed the tech has to reset the maintenance counter by going to Timers >
Maintenance > Reset Counter and selecting "Yes".
Reset
Defaults
Event
The controller has loaded default settings. This could have been because the user initiated a factory
reset from the RapidCore software or the controller memory has became corrupt. The controller will
need to be programmed with the proper settings if applicable.
Service
Complete
Event
The tech has performed service on the engine/generator and has reset the maintenance counter as
mentioned in "Service Required" above.
Exerciser
Bypass
Event
The exerciser, if enabled under Timers > Exerciser, has been skipped. This could happen if the
controller was otherwise running or powered off when an exerciser was scheduled to be performed.
Start
Exercise
Event
The controller has auto started to perform an exercise.
Stop
Exercise
Event
The controller has ran for the programmed exercise and is now shutting down.
Log
Cleared
Event
The controller Event History has been cleared either from user action (via the RapidCore software) or
because the controller memory was corrupt.
Modbus
Start
Event
The controller has auto start from a start command sent to it's RS485 Modbus port.
Modbus
Stop
Event
The controller has auto stopped from a stop command sent to it's RS485 Modbus port.
Genset
Disable
Event
Applies to the Kubota electronic engine. Level 3 shutdown has occurred.
Engine
Started
Event
The engine has successfully started and entered the RUN mode.
J1939
Remote
Event
The controller has auto started due to a command send over it's CAN J1939 port.
Idle Speed
Event
The controller has entered IDLE mode either from the idle switched input, the warmup or cooldown
idle feature under Engine Logic or some other reason. Under speed, under frequency, and under
voltage warnings and failures are disabled.
Rated
Speed
Event
The controller has exited idle mode and has gone back into normal running.
Sensor 1
Run
Event
The controller has auto started due to a auxiliary sensor 1 "start on low" or "start on high" request.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...