Installation
9
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Communications Connector (J6)
Terminal
Name
Description
J6-1
No Connection
No Connection
J6-2
No Connection
No Connection
J6-3
No Connection
No Connection
J6-4
CAN-H
Communications line for CAN Bus (J1939)
J6-5
CAN-L
J6-6
CAN-Shield
Connect the shield of the twisted pair cable to this terminal
J6-7
Speed Sensing A
Connect to a magnetic pickup, tachometer, or a flywheel alternator. Not polarity
sensitive and not required if using AC voltage terminals for speed sensing.
J6-8
Speed Sensing B
Connect to a magnetic pickup, tachometer, or a flywheel alternator. Not polarity
sensitive and not required if using AC voltage terminals for speed sensing.
J6-9
No Connection
No Connection
J6-10
No Connection
No Connection
Generator AC Voltage (J5)
Terminal
Name
Description
J5-1
Phase A
Connect to Phase A of the generator
J5-2
Phase B
Connect to Phase B of the generator
J5-3
Phase C
Connect to Phase C of the generator
J5-4
Neutral
Connect to neutral of the generator
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...