Settings
62
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
4.7
Communications
The controller has the ability to communicate with other systems over communication buses. The following sections relate to
settings associated with communications.
4.7.1
CAN Bus (J1939)
This page gives a very short overview of J1939 support (electronic engines). For detailed information about J1939 and all
related settings please refer to the J1939 Reference Manual. The manual can be found at
.
Name
Range
Default
Description
ECM Model
Generic J1939
John Deere JDEC
Volvo EMS
This is not a
complete list. See
the J1939 User
Manual for the full
list.
Generic
J1939
Choose one of the compatible ECM modules from the list.
ECM
Communicati
on Failure
Enable ~ Disable
Disable
If no CAN messages are received for more than 6 seconds, the controller
shuts down the engine.
DTC Display
Disable
Global Enable
Running Enable
Disable
Enables or disables active fault messages (DM1) monitoring.
Active DTC
Log
Enable ~ Disable
Disable
Enables or disables the storing of active faults (DM1).
Read Stored
DTC
Enable ~ Disable
Disable
Enables or disables the ability to request stored fault codes from the ECM
(DM2).
Auto Power
ECM
Enable ~ Disable
Disable
When enabled, the fuel relay is enabled in Auto mode so that the ECM is
already booted up and initialized before the user decides to start the engine.
ECM Power
Delay
5 ~ 30 s in 1 s
increments
10 s
Used in conjunction with Auto Power ECM. When the engine shuts down,
the controller waits for the time specified by the ECM Power Delay before
turning on the fuel relay. This prevents unwanted start ups due to the
engine not being completely shut down.
Cummins
PGNs
Disable or
Sending Enable
Sending
Enable
Enables or disables the broadcasting of PGNs required by some Cummins
engines.
SPN
Conversion
Version 1
Version 2
Version 3
Version 3
Select the SPN conversion method.
EMS2B
Frequency
Select
Primary
Secondary
Primary
For Volvo EMS2B Engine Control Modules only.
EMS2B
Accelerator
Pedal
40.0 ~ 60.0 % in
0.1 % increments
50.0 %
For Volvo EMS2B Engine Control Modules only.
4.8
Other Config
This section contains miscellaneous settings.
4.8.1
Password
A password is required to change certain settings. The Password menu is used to change this password and control if and
when the user is prompted for a password.
Other Config > Passcode:
Name
Range
Default
Description
Bypass
Disable or Enable
Disable
If enabled a password is not required to change settings.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...