Chapter 12
12 Connection of closing edge protection
CAUTION
This work must only be performed by
qualified, trained persons.
NOTICE
Main closing edge:
The leading edge of the
door.
Activating the sensor will disable automatic
operation in the closing direction.
Secondary closing edge:
The trailing edge of
the door.
Activating the sensor will disable automatic
operation in the opening direction.
When testable sensors for the protection of the closing
edge are connected, the control unit has to be
configured to the sensors via the DIP switches.
Main closing edge sensor connection:
• Set DIP switch 1 to ON and DIP switch 2 to OFF.
Secondary closing edge sensor connection:
• Set DIP switch 1 to ON and DIP switch 3 to OFF.
Sensors connected to both main and secondary closing
edges:
• Set DIP switch 1 to ON and DIP switches 2 and 3 to
OFF.
Fig. 12.1.1
Control unit DIP switch
8
7
6
5
4
3
2
1
N
O
8
7
6
5
4
2
1
3
ON
3
ON
Test high active
OFF
Test low active
2
ON
Sensor test for secondary closing edge activated
OFF
Sensor test for secondary closing edge deactivated
1
ON
Sensor test for main closing edge activated
OFF
Sensor test for main closing edge deactivated
Table 12.1.1 Closing edge sensors
DIP switch settings