53
CS 80 MAGNEO
10-2022
DL3316-010
Installation and Troubleshooting Manual
Chapter 9
9.1.17 Secure end stop at desired door closed position.
1. Loosen the end stop screws on the side where the
connections are made.
2. Move the door to the desired position.
3. Move end stop next to the door panel and tighten the
end stop fasteners.
NOTICE
The end stop may only be moved to the inside
by a certain maximum dimension Y:
34.4" [875 mm] operator =>7.9" [200 mm].
39.4" [1000 mm] operator =>9.5" [250 mm].
48.2" [1125 mm] operator =>11.8" [300 mm].
Fig. 9.1.16 End stop final position
3.
3.
Y
4.
1.
Y
2.
9.1.18 Secure opposite end stop in door open position.
1. Loosen opposite side end stop screws.
2. Move door to desired open position.
3. Move end stop next to door panel.
4. Tighten end stop screws.
NOTICE
The end stop may only be moved to the outside
by a maximum dimension (Y):
34.4" [875 mm] operator =>7.9" [200 mm].
39.4" [1000 mm] operator =>9.5" [250 mm].
48.2" [1125 mm] operator =>11.8" [300 mm].
3.
2.
1.
Y
4.
Y
Fig. 9.1.17 End stop final position
9.1.19 Door panel to wall maximum distance.
NOTICE
The distance between the door panel and wall
must not exceed 5/16" [7.94 mm].
9.1.20 Connection of external accessories.
1. Connect all external accessories except for safety
sensors. Refer to cable channel instructions.
9.1.21 Continue with system commissioning.
Reference Chapter 13.
.3125" max.
[8 mm max.]
Fig. 9.1.18 Door panel to wall minimum distance