LP Panelized Baghouse 684LP - 882LP
Explosion Vent
Personal injury, death, and/or property damage can result from material discharge during venting.
The material discharged during the venting of an explosion must be safely directed outdoors away from areas
occupied by personnel to reduce risk of personal injury and/or property damage.
The risk of personal injury and/or property damage can be minimized or avoided by locating vented equipment
outside buildings and away from normally occupied areas.
Explosion vents should be inspected regularly to confirm physical and operational condition. Replace any damaged
parts immediately.
Standard explosion vents are intended for outdoor installations only.
Unless otherwise noted, the explosion venting calculations are based on formulas from NFPA-68 for outdoor applications only, with
no duct or obstructions on the explosion vent panel.
Contact Donaldson Torit for assistance in calculating specific venting requirements for equipment.
NFPA 68 can provide guidance on both the frequency of and appropriate details for inspections.
Platform/Ladder
Collector may be equipped with a platform/ladder system for gaining access to the clean-air plenum for filter bag changeout. For all
ladders over 24-ft installed November 19, 2018 or later, OSHA requires a ladder safety system or personal fall arrest system. As a
convenience, Donaldson offers ladder safety systems as an option.