19
3.1.3 Remove the Transport Fasteners from the Compressor
(Figure 3-3: Removing the Side Panel)
If the side panel is locked, use a No. 2 Phillips screwdriver to remove the screws first. Hold
the side panel with your hand when the screws are being removed in order to prevent the
panel from falling. Then, pull outward first, then lift up to remove the side panel.
To place the side panel back in place, align it with the two bottom holes. One person should
support the side panel while the other person refastens the fixing screws.
After removing the side panel, please remove the compressor transport fasteners as shown
in the figure below (the compressor transport fasteners must be removed before operation,
if the transport fasteners are not removed, the compressor will easily generate abnormalities
in operation), and tighten the stud at a torque of 120±5kgf/cm
2
.
When moving the unit, the transport fasteners must be reinstalled.