Outdoor unit
The outdoor unit will have a large amount of air flow that discharges heat into the
atmosphere. Therefore, the outdoor unit should be installed in a clean area free of
debris, away from dirt and foreign objects that may block the condenser. In
addition, the outdoor unit must not be located near steam, hot air or flue gas
outlets. The outdoor unit should be located more than 60 inches away from walls,
obstructions, or adjacent equipment, and there should be no obstructions above
the equipment.
Do not install the outdoor unit in an area where the sound level of the normal
operation of the equipment may interfere with the work or living environment of
others.
The installation surface must not muddy.
Unit: inch
(Figure 3-2: Outer Unit Horizontal Clearance)