InfraSuite R Series – Air Cooled Type
72
Parameter
Setting Range
Description
Default Setting
Note
5.6.7 Setup-->Exceed Alarm Setting-->Air Side
Supply Air
Temp High
On/Off Setting
supply
air temperature
high alarm value
Off
68-122°F
Supply Air
Temp Low
On/Off Setting
supply
air temperature
low alarm value
Off
41-59°F
Return Air
Temp High
On/Off
Setting return air
temperature high
alarm value
On
95-131°F 113°F
Return Air
Temp Low
On/Off
Setting return air
temperature low
alarm value
Off
41-59°F
Supply Air
RH High
On/Off Setting
supply
air relative
humidity high
alarm value
Off
65-95%
Supply Air
RH Low
On/Off Setting
supply
air relative
humidity low
alarm value
Off
5-35%
Return Air
RH High
On/Off
Setting return air
relative humidity
high alarm value
Off
65-95%
Return Air
RH Low
On/Off
Setting return air
relative humidity
low alarm value
Off
5-35%
Cold Aisle Air
Temp High
On/Off
Setting cold aisle
air high
temperature
alarm value
Off Optional
sensor
68-122°F
Cold Aisle Air
Temp Low
On/Off
Setting cold aisle
air temperature
low alarm value
Off Optional
sensor
41-59°F
Содержание InfraSuite RDA037
Страница 11: ...11 Unit inch Figure 2 4 Outdoor Unit Appearance and Dimensions...
Страница 63: ...63 5 5 2 Data History Path Main Page Measurement Data History...
Страница 64: ...InfraSuite R Series Air Cooled Type 64 5 5 3 Warning Path Main Page Maintenance Warning...
Страница 65: ...65 5 5 4 Historical Event Path Main Page Maintenance Historical Event...
Страница 88: ......
Страница 89: ......
Страница 90: ......
Страница 92: ...5013295900...