69
Parameter
Setting Range
Description
Default Setting
Note
Leak
Shutdown
On/Off
The water
leakage alarm
may shut down
the unit
Off
Compressor
Preheating
On/Off
The first time a
unit starts
operating, the
compressor
needs
preheating
On
Heater
Enable
On/Off
Enable the
heater function if
a unit includes a
heater
Off
Humidifier
Enable
On/Off
Enable the
humidifier
function if a unit
includes a heater
Off
5.6.3 Setup-->Group Control Setting
Group Mode
On/Off
Enable Group
Control Function
Off
Group
Number
0-99
Amount of
cooling units in a
group
0
Backup
Number
0-99
Amount of
cooling units that
start if one unit
shuts down
0
Over Heat
Backup
On/Off
When the return
air is at a high
temp, the
standby cooling
unit will start
Off