InfraSuite R Series – Air Cooled Type
48
Step 2
Set up the dip switch for the temperature and humidity sensor. The sensor appears as in
Figure 3-30
. For the specific setup method, refer to
Table 3-3
below.
(Figure 3-30: Dip Switch Appearance)
Table 3-3: Instructions for Operating the Temperature and Humidity Sensor Dip Switch
Detection
Location
Addressing
Dip Switch Serial Number
1
2
3
4
5
Air
return 0
OFF OFF OFF OFF OFF
Air supply
1
ON
OFF
OFF
OFF
ON
Remote
side
0
OFF OFF OFF OFF OFF
1
ON OFF OFF OFF OFF
2
OFF ON OFF OFF OFF
3 ON
ON
OFF
OFF
OFF
4 OFF
OFF
ON
OFF
OFF
5
ON OFF ON OFF OFF
6 OFF
ON
ON
OFF
OFF
7 ON
ON
ON
OFF
OFF
8
OFF OFF OFF ON OFF
NOTE:
The default setting for the temperature and humidity sensor is 0.
"5" on the dip switch is the RS485 terminal resistance.
Addressing 0-4 is Cold Aisle1-5; 5-9 is Hot Aisle1-5.