InfraSuite R Series – Air Cooled Type
68
5.6
Summary of Parameters Settings
Parameter
Setting Range
Description
Default Setting
Note
5.6.1 Setup-->Set Point Setting
Control Type
Return Air
Choose a control
type that suits
the needs of the
computer room.
Supply Air
It is
recommended
to use supply
air temperature
control for row
cool.
Supply Air
Cold Aisle
Hot Aisle
Temperature
Setpoint
82.4-104°F
(Return Air/Hot
Aisle)
The air
temperature
control target
75°F
62.6-82.4°F
(Supply Air/Cold
Aisle)
Humidity
Setpoint
15-80%
The air relative
humidity control
target
50%
Temperature
Control Band
0.0-3.6°F
The air
temperature
control band
1.8°F
Humidity
Control Band
0-20%
The air relative
humidity control
band
20%
5.6.2 Setup-->Controller Setting
Auto Recover On/Off
After Power
Recover
On
Keep
previous setting
Off
Standby
On
Delay Time
1-30 sec
After Power
Recover
There is a delay
time when a unit
starts to operate
5 sec