73
Parameter
Setting Range
Description
Default Setting
Note
5.6.8 Setup-->Exceed Alarm Setting-->Refrigerant Side
Discharge
Pressure
Over High
On/Off
Display or not
On
If it needs to be
changed,
please contact
Delta.
Suction
Pressure
Over Low
On/Off
Display or not
On
Discharge
Temp Over
High
On/Off
Display or not
On
Suction Temp
Over Low
On/Off
Display or not
On
5.6.9 Setup-->General Settings
Date Format ymd/dmy/mdy
Setting Date
display format
ymd
Date Settings yyyy/mm/dd
Setting Date
yyyy/mm/dd
Time Settings
00:00:00-
23:59:59
Setting Time
XX:XX:XX
Time Zone
Settings
UTC-12:00-
+13:00
Setting Time
Zone
UTC+8:00
ID 1-254
Setting ID in
Group
1
Unit °C/°F
Setting
Temperature
Unit
°F
Language EN/SC/TC
Setting
Language
EN
Baudrate 9600/19200
Setting Modbus
Baudrate
9600