85
P6.01
PID digital
setting
0.0%
~
100.0%
1
50
○
P6.02
PID feedback
source
0
:
VI
1
:
CI
3
:
VI-CI
4
:
Pulse setting
5
:
Communication setting
6
:
VI+CI
7
:
MAX(|VI|+|CI|)
8
:
MIN(|VI|,|CI|)
1
0
○
P6.03
PID action
direction
0
:
Forward action
1
:
Reverse action
1
0
○
P6.04
PID setting
feedback range
0
~
65535
1
1000
○
P6.05
Proportional gain
KP1
0.0
~
100.0
0.1
20.0
○
P6.06
Integral time TI1
0.01S
~
10.00S
0.01S
2.00S
○
P6.07
Differential time
TD1
0.000S
~
10.000S
0.001S
0.000S
○
P6.08
Cut-off frequency
of PID reverse
rotation
0.00 to maximum frequency
0.01
2.00HZ
○
P6.09
PID deviation
limit
0.0%
~
100.0%
0.1%
0.0%
○
P6.10
PID differential
limit
0.00%
~
100.00 %
0.01%
0.10%
○
P6.11
PID setting
0.00
~
650.00S
0.01S
0.00S
○