86
change time
P6.12
PID feedback
filter time
0.00
~
60.00S
0.01S
0.00S
○
P6.13
PID output filter
time
0.00
~
60.00S
0.01S
0.00S
○
P6.14
Reserved
○
P6.15
Proportional gain
KP2
0.0
~
100.0
0.1
20.0
○
P6.16
Integral time TI2
0.01S
~
10.00S
0.01
2.00S
○
P6.17
Differential time
TD2
0.000S
~
10.000S
0.001S
0.000S
○
P6.18
PID parameter
switchover
condition
0
:
No switchover
1
:
Switchover via Xi
2
:
Automatic switchover
based on deviation
3
:
Automatic switchover
based on running frequency
0.01
0
○
P6.19
PID parameter
switchover
deviation 1
0.0%
~
P6.20
0.1
%
20.0
%
○
P6.20
PID parameter
switchover
deviation 2
P6.19
~
100.0 %
0.1
%
80.0
%
○
P6.21
PID initial value
0
.
0%
~
100.0 %
1
0
.
0%
○
P6.22
PID initial value
holding time
0.00
~
650.00S
0.01S
0.00S
○
P6.23
Maximum
0.00%
~
100.00%
0.01%
1.00%
○