217
fault protection action.
If the over-speed detection time is 0.0s, the over-speed detection
function is disabled.
PA.65
Detection value of too large speed
deviation
Setting Range:
0.0%
~
50.0%
20.0%
PA.66
Detection time of too large speed
deviation
Setting Range:
0.0s
~
60.0s
5.0s
This function is valid only when the AC drive runs in the CLVC mode.
If the AC drive detects the deviation between the actual motor rotational speed detected by
the AC drive and the set frequency is greater than the value of PA.65 and the lasting time
exceeds the value of PA.66, the AC drive reports E-30 and according to the selected fault
protection action.
If PA.66 (Detection time of too large speed deviation) is 0.0s, this function is disabled.
6.12 Multi-Reference and Simple PLC Function
(
Group Pb
)
The DGI900 multi-reference has many functions. Besides multi-
speed, it can be used as the setting source of the V/F separated
voltage source and setting source of process PID. In addition, the
multi-reference is relative value.
Pb.00~15
Multi-reference 0 to Multi-reference
15
Setting Range:
-100.0%
~
100.0%
0.0%
Multi-reference can be the setting source of frequency, V/F separated voltage and process
PID. The multi-reference is relative value and ranges from -100.0% to 100.0%.