When this terminal becomes ON, the AC drive's current running
time is cleared. This function must be supported by P2.40 and
P2.41.
P3.10
VI function selection(DI)
Setting Range
:
0
~
50
0
P3.11
CI function selection(DI)
Setting Range
:
0
~
50
0
The functions of these parameters are to use AI as DI. When AI is used as DI, the AI state is
high level if the AI input voltage is 7 V or higher and is low level if the AI input voltage is 3V
or lower. The AI state is hysteresis if the AI input voltage is between 3 V and 7 V. A1-10 is
used to determine whether high level valid or low level valid when AI is used as DI. See the
following figure 6-18.
The setting of AIs (used as DI) function is the same as that of Xs. For details, see the
descriptions of group P3.