189
P6.09
PID deviation limit
Setting Range
:
0. 0%
~
100.0%
0.01%
If the deviation between PID feedback and PID setting is smaller
than the value of P6.09, PID control stops. The small deviation
between PID feedback and PID setting will make the output
frequency stabilize, effective for some closed-loop control
applications.
P6.10
PID differential limit
Setting Range
:
0.
00%
~
100.00%
0.10%
It is used to set the PID differential output range. In PID control,
the differential operation may easily cause system oscillation.
Thus, the PID differential regulation is restricted to a small range.
P6.11
PID setting change time
Setting Range
:
0.00s
~
650.00s
【
0.00s
】
The PID setting change time indicates the time required for PID
setting changing from 0.0% to 100.0%. The PID setting changes
linearly according to the change time, reducing the impact caused
by sudden setting change on the system.
P6.12
PID feedback filter time
Setting Range
:
0.00
~
60.00s
【
0.00s
】
P6.13
PID output filter time
Setting Range
:
0.00
~
60.00s
【
0.00s
】
P6.12 is used to filter the PID feedback, helping to reduce interference on the feedback but