130
▲and▼ or the terminal UP/DOWN function is cleared.
1
“
:
Retentive”
:
If P0-22 is set to 1, the digital setting frequency value is the set
frequency at the moment when the AC drive stops. The modification by using keys ▲ and
▼ or the terminal UP/DOWN function remains effective.
P0.23
Base frequency for UP/DOWN
modification during running
Setting Range
:
0
~
1
0
0
:
Running frequency
;
1
:
Set frequency.
This parameter is valid only when the frequency source is digital setting.
It is used to set the base frequency to be modifie
d by using keys and or the
terminal UP/DOWN function. If the running frequency and set
frequency are different, there will be a large difference between
the AC drive's performance during the acceleration/deceleration
process.
P0.24
Binding command source
to frequency source
Setting Range
:
0000
~
9999
0000
Unit's digit:
Binding operation panel command to frequency source.
Ten's digit:
Binding terminal command to frequency source.
Hundred's digit:
Binding communication command to frequency source.
Thousand’s digit:
Binding automatic running command to frequency source
It is used to bind the four running command sources with the nine frequency sources,
facilitating to implement synchronous switchover.