corresponding to P3.21 to P3.25, Curve 3 corresponding to P3.26
to P3.30.
P3.37
Setting for VI less
than minimum input
Setting Range
:
333
~
000
321
This parameter is used to determine the corresponding setting when the analog input
voltage is less than the minimum value. The unit's digit, ten's digit and hundred's digit of this
parameter respectively correspond to the setting for VI and CI.
If the value of a certain digit is 0, when analog input voltage is less than the minimum input,
the corresponding setting of the minimum input (P3.16
、
P3.22
、
P3.26) is used.
If the value of a certain digit is 1, when analog input voltage is
less than the minimum input, the corresponding value of this
analog input is 0.0%.
P3.38
X1 delay time
Setting Range
:
0.0s
~
3600.0s
0.0s
P3.39
X2 delay time
Setting Range
:
0.0s
~
3600.0s
0.0s
P3.40
X3 delay time
Setting Range
:
0.0s
~
3600.0s
0.0s
These parameters are used to set the delay time of the AC drive when the status of X
terminals changes.
Currently, only X1, X2 and X3 support the delay time function.
P3.41
X valid mode
Selection 1
Setting Range
:
00000
~
11111
00000