Chapter 6 Description of Function Codes
6.1 Basic Parameters
(
Group P0
)
P0.00
Control Mode
Setting Range
:
0
~
2
0
0
:
V/F Control
:
It is applicable to applications with low load requirements or applications
where one AC drive operates multiple motors, such as fan and pump.
1
:
Sensorless flux vector control (SFVC)
:
It indicates open-loop vector control, and is
applicable to high-performance control applications such as machine tool, centrifuge, wire
drawing machine and injection molding machine. One AC drive can operate only one motor.
2
:
Closed-loop vector control(CLVC)
:
It is applicable to high-accuracy speed control or
torque control applications such as high-speed paper making machine, crane and elevator.
One AC drive can operate only one motor. An encoder must be installed at the motor side,
and a PG card matching the encoder must be installed at the AC drive side.
P0.01
Main frequency source 1
selection
Setting Range
:
0
~
9
0
0
:
Digital setting (non-retentive at power failure)
:
You can change the set frequency by
pressing
▲
▲and▼on the operation panel. When the AC drive is powered on again after power
failure, the set frequency reverts to the value of P0.02 .
1
:
Digital setting (retentive at power failure)
:
You can change the set frequency by
pressing keys
▲
▲and▼on the operation panel (or using the UP/DOWN functions of input
terminals)
.
When the AC drive is powered on again after power failure, the set frequency
is the value memorized at the moment of the last power failure.
2
:
VI analog setting(VI-GND).
0–10 V voltage input
3
:
CI analog setting (CI-GND).
0–10 V voltage input or 4–20 mA current input, determined