Zero-speed running
(
no output at stop
)
If the AC drive runs with the output frequency of 0, the terminal becomes ON. If the AC drive
is in the stop state, the terminal becomes OFF.
6
:
Motor overload pre-warning
The AC drive judges whether the motor load exceeds the overload pre-warning threshold
before performing the protection action. If the pre-warning threshold is exceeded, the
terminal becomes ON. For motor overload parameters, see the descriptions of PA.00 to
PA.02.
7
:
AC drive overload pre-warning
The terminal becomes ON 10s before the AC drive overload protection action is performed.
8
:
Set count value reached
:
The terminal becomes ON when the count value reaches the
value set in PE.08.
9
:
Designated count value reached
:
The terminal becomes ON when the designated value
reaches the value set in PE.09.
10
:
Length reached
:
The terminal becomes ON when the detected actual length exceeds
the value set in PE.05.
11
:
PLC cycle complete
:
When simple PLC completes one cycle, the terminal outputs a
pulse signal with width of 250 ms.
12
:
Current running time reached
:
If the current running time of the AC drive exceeds the
time set in P2.51, the terminal becomes ON.
13
:
Frequency limited
If the set frequency exceeds the frequency upper limit or lower limit and the output