and the duration exceeds the zero current detection delay time, the corresponding DO
becomes ON. The zero current detection is shown in the following figure 6-13.
Figure 6-13 Zero current detection
P2.34
Output overcurrent
threshold
Setting Range
:
0.0%
~
300.0%
5.0%
P2.35
Output overcurrent
detection delay time
Setting Range
:
0.01s
~
600.00s
0.10s
If P2.34 is 0.0%, no detection; 0.1%
~
300%(rated motor current)
If the output current of the AC drive is equal to or higher than the overcurrent threshold and
the duration exceeds the detection delay time, the corresponding DO becomes ON. The
output overcurrent detection function is shown in the following figure6-14.