with function 38 "PID integral pause" is ON or not.
Ten's digit
:
Whether to stop integral operation when the output reaches the limit
;
0
:
Continue integral operation
;
1
:
Stop integral operation.
If "Stop integral operation" is selected, the PID integral operation
stops, which may help to reduce the PID overshoot.
P6.26
Detection value of PID
feedback loss
Setting Range
:
0.1%
~
100.0%
【
0.0%
】
P6.27
Detection time of PID
feedback loss
Setting Range
:
0.0s
~
20.0s
【
1s
】
These parameters are used to judge whether PID feedback is
lost. Not judging feedback loss when set P6.26 to 0.0%.
If the PID feedback is smaller than the value of P6.26 and the
lasting time exceeds the value of P6.27, the AC drive reports
Err31 and acts according to the selected fault protection action.
P6.28
PID operation at stop
Setting Range
:
0
~
1
【
0
】
0
:
No PID operation at stop
;
1
:
PID operation at stop
It is used to select whether to continue PID operation in the state of stop. Generally, the PID
operation stops when the AC drive stops.
6.8 Operation Panel and Display
(
Group P7
)
P7.00
REV key function selection
Setting Range
:
0
~
4
3
0
:
REV key disabled