SiUS331708EA
Symptom-Based Troubleshooting
Service Diagnosis
148
2.3
With Gas Furnace
2.4
Gas Furnace Lockout Reset
Furnace lockout is characterized by a non-functioning furnace (circulator blower may be running continuously)
providing a diagnostic LED code located on the furnace board.
Lockout results when a furnace control detects abnormal conditions. If the furnace is in "lockout", the following
methods can be used to clear the error.
a. Turn the remote controller off to clear the error. If the error is not cleared, proceed to next step.
b. Set the setting temperature to maximum, then turn the remote controller on.
c. Turn the remote controller off.
d. Turn the remote controller on after around 15 seconds from procedure c.
The procedures b, c, and d will not work during certain outdoor unit operations, i.e. defrost, startup, compressor
stop, service mode etc.
If the LED of the
ON/OFF
button is flashing when you turn the remote controller on, you cannot clear the error
with the method above. In that case, the error must be cleared using the gas furnace. Refer to the gas furnace
operation manual for more details.
Symptom
Supposed Cause
1
The gas furnace does not start operation.
The gas furnace does not start operation while the compressor
is during operation or under stop-control, or right after defrost IN
or defrost OUT. Wait until the operation becomes stable.
2
Operation does not switch from heat pump to gas furnace in
spite of low room temperature. Operation does not switch
from gas furnace to heat pump even though the room
temperature is nearing the set temperature.
This function is performed only with outdoor units which support
automatic switching between gas furnace and heat pump
interlocking with room temperature.
Some models are enabled to support automatic switching
between gas furnace and heat pump interlocking with outdoor
air temperature by setting heat pump lockout on an outdoor unit
side. However, the compressor stops while gas furnace is
during operation.
It is possible that temperature setting for switching from heat
pump to gas furnace and from gas furnace to heat pump is not
appropriate. Confirm the field setting 11(21)-1 and 11(21)-2 and
change the temperature setting for switching as needed. Refer
to
2-Step Thermostat Processing (CXTQ-TA Models)
on
page 84 for details.
Operation does not switch from gas furnace to heat pump for a
predetermined period of time after ignition of gas furnace to
avoid frequent switching. The period of time can be changed at
the field setting 11(21)-3. Refer to
Gas Furnace Control
(CXTQ-TA Models)
on page 82 for details.
3
AA-03
(Gas furnace abnormality) is indicated on the remote
controller while no error is indicated on the PCB of the gas
furnace.
In some cases of gas furnace abnormality, error indication on
the remote controller is retained even after the abnormality is
removed. Execute combustion heating operation once or reset
the power source.
4
The gas furnace does not stop even when the room
temperature exceeds the set temperature.
The gas furnace does not stop during defrost/oil return
operation to prevent cold air from blowing out due to fan residual
operation. At the field setting 11(21)-3, the gas furnace setting
can be changed not to operate during defrost/oil return
operation.
5
The airflow rate indication on the remote controller is not
consistent with the actual airflow rate of the indoor unit.
The airflow rate of the indoor unit during gas furnace
combustion heating depends on the intensity of combustion.
Therefore, the airflow rate of the indoor unit does not reflect the
airflow setting of the remote controller.
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...