Field Settings from Outdoor Unit
SiUS331708EA
115
Field Settings and Test Operation
2.4
Setting Mode 2
No.
Setting item
Description
1
Cool / heat unified
address
Sets address for cool / heat unified operation.
2
Low noise / demand
address
Address for low noise / demand operation
3
Test operation settings
Used to conduct test operation without making changes to the
PCB and replacing the refrigerant, after the completion of
maintenance.
4
Existing pipe
connection
The field setting is required based on the field gas piping size and
the field liquid pipe with or without thermal insulation.
When there is no thermal insulation, the airflow rate of the
operating indoor unit may decrease due to protection.
5
Indoor unit forced fan H
Allows forced operation of indoor fan while unit is stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
7
SC adjustment
Subcooling adjustment for refrigerant addition.
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
10
Defrost changeover
setting
Changes the temperature condition for defrost and sets to quick
defrost or slow defrost.
12
External low noise /
demand setting
Reception of external low noise or demand signal
13
AIRNET address
Set address for AIRNET.
14
Switch over ambient
setting
When the temperature is lower than the set ambient temperature,
operate the gas furnace instead of heat pump heat.
(Gas furnace operation requiring signal : ON)
15
Switch over ambient
setting
(Release differential)
Differential temperature for release of "Switch over ambient
setting".
16
Setting of heat pump
lockout 1
Make this setting for heat pump lockout.
19
Emergency automatic
heat pump lockout
Heat pump is automatically locked out in the event of a system
failure.
20
Additional refrigerant
charge operation
setting
Carries out additional refrigerant charge operation.
21
Refrigerant
recovery / vacuuming
mode setting
Sets to refrigerant recovery or vacuuming mode.
22
Night-time low noise
setting
Sets automatic nighttime low noise operation in a simple way.
The operating time is based on Starting Set and Ending Set.
25
Setting of low noise
level
Sets low noise level when the low noise signal is received.
26
Night-time low noise
operation start setting
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
27
Night-time low noise
operation end setting
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
28
Power transistor check
mode
∗
Check after
disconnection of
compressor wires
Used for trouble diagnosis of DC compressor. Since the waveform
of inverter is output without wiring to the compressor, it is
convenient to probe whether the trouble comes from the
compressor or PCB.
29
Capacity precedence
setting
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out low noise
operation and night-time low noise operation.
30
Demand setting 1
Changes target value of power consumption when demand control
1 is received.
32
Constant demand
setting
Enables demand control 1 without external input. (Effective to
prevent a problem that circuit breaker of small capacity is shut
down due to large load.)
37
Setting of heat pump
lockout 2
Make this setting for heat pump lockout.
41
Cooling comfort setting Selects comfort level of VRT cooling.
The numbers in the No. column represent the number of times to press the
SET
(BS2)
button.
Selection of setting items
Selection of setting conditions
Press the
MODE (BS1)
button for 5
seconds and enter the setting mode
2.
Press the
SET (BS2)
button and
select a setting item according to the
LED pattern shown in the table on
the right.
↓
Press the
RETURN (BS3)
button
and decide the item. (The present
setting condition is shown.)
Press the
RETURN (BS3)
button
and return to the initial status of
setting mode 2.
∗
If you become unsure of how to
proceed, press the
MODE (BS1)
button and return to the setting
mode 1.
Press the
SET (BS2)
button and
select to the setting condition you
want.
↓
Press the
RETURN (BS3)
button and
decide the condition.
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...