SiUS331708EA
Field Settings from Outdoor Unit
Field Settings and Test Operation
130
Heat pump lockout temperature
Heat pump would be locked out when the outdoor air temperature is smaller than the heat pump lockout
temperature. This setting is only effective when heat pump lockout mode has been set.
When connecting with multiple gas furnaces, the field setting both 11(21)-1, 2 of indoor unit must be set to
07
.
For indoor unit setting, see indoor unit installation manual.
Heat pump lockout release differential
Heat pump would be resumed when the outdoor air temperature is recovered by differential above the heat pump
lockout temperature.
Automatic lockout
When heat pump lockout mode has been set, the auto backup function will automatically be set. This will allow
the auxiliary or secondary heat source to be automatically energized in the event of a system failure related to
outdoor units.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory setting
57
Heat pump
lockout
temperature
k
k
k
k
h
h
k
–26.1°C (–15°F)
k h h h h h h
∗
–23.3°C (–10°F)
k h h h h h k
–20.5°C (–5°F)
k h h h h k h
–17.7°C (0°F)
k h h h h k k
–15°C (5°F)
k h h h k h h
–12.2°C (10°F)
k h h h k h k
–9.4°C (15°F)
k h h h k k h
–6.6°C (20°F)
k h h h k k k
–3.8°C (25°F)
k h h k h h h
–1.1°C (30°F)
k h h k h h k
1.6°C (35°F)
k h h k h k h
4.4°C (40°F)
k h h k h k k
7.2°C (45°F)
k h h k k h h
10°C (50°F)
k h h k k h k
Forced heat
pump lockout
k h h k k k h
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory setting
47
Heat pump
lockout
release
differential
k
k
h
k
k
k
k
2.8°C (5°F)
k h h h h h h
5.6°C (10°F)
k h h h h h k
∗
8.3°C (15°F)
k h h h h k h
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...