SiUS331708EA
Field Settings from Outdoor Unit
Field Settings and Test Operation
118
The numbers in the No. column represent the number of times to press the
SET (BS2)
button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory setting
14
Switch over ambient
setting
k
h
h
k
k
k
h
–20.5°C (–5°F)
k h h h h h h
k h h h h h k
k h h h h k h
–17.7°C (0°F)
k h h h h k k
–15.0°C (5°F)
k h h h k h h
–12.2°C (10°F)
k h h h k h k
–9.4°C (15°F)
k h h h k k h
∗
–6.6°C (20°F)
k h h h k k k
–3.8°C (25°F)
k h h k h h h
–1.1°C (30°F)
k h h k h h k
1.6°C (35°F)
k h h k h k h
4.4°C (40°F)
k h h k h k k
7.2°C (45°F)
k h h k k h h
10°C (50°F)
k h h k k h k
Gas furnace operation only
k h h k k k h
Heat pump operation only
k h h k k k k
15
Switch over ambient
setting
(Release differential)
k
h
h
k
k
k
k
2.8°C (5°F)
k h h h h h h
5.6°C (10°F)
k h h h h h k
∗
8.3°C (15°F)
k h h h h k h
16
Setting of heat pump
lockout 1
k
h
k
h
h
h
h
OFF
k h h h h h k
∗
ON
k h h h h k h
19
Emergency automatic
heat pump lockout
k
h
k
h
h
k
k
OFF
k h h h h h k
ON
k h h h h h h
∗
20
Additional refrigerant
charge operation setting
k
h
k
h
k
h
h
Refrigerant charging: OFF
k h h h h h k
∗
Refrigerant charging: ON
k h h h h k h
21
Refrigerant recovery /
vacuuming mode setting
k
h
k
h
k
h
k
Refrigerant recovery /
vacuuming: OFF
k h h h h h k
∗
Refrigerant recovery /
vacuuming: ON
k h h h h k h
22
Night-time low noise
setting
k
h
k
h
k
k
h
OFF
k h h h h h h
∗
Level 1 (outdoor fan with 6 step or lower)
k h h h h h k
Level 2 (outdoor fan with 5 step or lower)
k h h h h k h
Level 3 (outdoor fan with 4 step or lower)
k h h h h k k
25 Setting of low noise level
k
h
k
k
h
h
k
Level 1 (outdoor fan with 6 step or lower)
k h h h h h k
Level 2 (outdoor fan with 5 step or lower)
k h h h h k h
∗
Level 3 (outdoor fan with 4 step or lower)
k h h h k h h
26
Night-time low noise
operation start setting
k
h
k
k
h
k
h
About 08:00 PM
k h h h h h k
About 10:00 PM (factory setting)
k h h h h k h
∗
About 12:00 AM
k h h h k h h
27
Night-time low noise
operation end setting
k
h
k
k
h
k
k
About 06:00 AM
k h h h h h k
About 07:00 AM
k h h h h k h
About 08:00 AM (factory setting)
k h h h k h h
∗
28
Power transistor check
mode
k
h
k
k
k
h
h
OFF
k h h h h h k
∗
ON
k h h h h k h
29
Capacity precedence
setting
k
h
k
k
k
h
k
OFF
k h h h h h k
∗
ON
k h h h h k h
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...