Troubleshooting by Error Code
Service Diagnosis
156
4.3
Error Code Indication by Outdoor Unit PCB
Selection of setting item
Confirmation of error 1
To enter the monitor mode, press
the
MODE (BS1)
button when in
“Setting mode 1”.
Press the
SET (BS2)
button and set
the LED display to a setting item.
Press the
RETURN (BS3)
button
once to display "First digit" of error
code.
Confirmation of error 2
Press the
SET (BS2)
button once to
display "Second digit" of error code.
Press the
RETURN (BS3)
button
and switches to the initial status of
“Monitor mode”.
∗
Press the
MODE (BS1)
button and
return to “Setting mode 1”.
Confirmation of error 3
Press the
SET (BS2)
button once to
display "error location".
Detailed
description
on next
page.
Confirmation of error 4
Press the
SET (BS2)
button once to
display "master or slave 1 or slave 2"
and "error location".
Monitor mode
Error Description
Error Code
PCB abnormality
E1
Abnormal high pressure switch
High pressure switch activated
E3
Abnormal low pressure switch
Low pressure switch activated
E4
Compressor lock
Detection of inverter compressor lock
E5
Overload, overcurrent,
abnormal lock of outdoor fan motor
Detection of DC fan 1 motor lock
E7
Detection of DC fan 2 motor lock
Electronic expansion valve
abnormality
Main
E9
Subcooling
Abnormal discharge pipe temperature
Abnormal Tdi
F3
Defective thermistor of outdoor air
temperature
Defective Ta sensor (short)
H9
Defective discharge pipe thermistor
Defective Tdi sensor (short)
J3
Defective suction pipe thermistor
Defective Ts1 sensor (short)
J5
Defective Ts2 sensor (short)
Defective outdoor heat exchanger
deicer thermistor
Defective Tb sensor (short)
J6
Defective outdoor heat exchanger
liquid pipe thermistor
Defective TI sensor (short)
J7
Defective subcooling heat exchanger
gas pipe thermistor
Defective Tsh sensor (short)
J9
Defective sensor of high pressure
Defective Pc sensor (short)
JA
Defective sensor of low pressure
Defective Pe sensor (short)
JC
Defective PCB (for inverter
compressor)
Defective IPM
L1
Abnormal current sensor offset
Abnormal IGBT
Defective current sensor
Abnormal SP-PAM overvoltage
Abnormal interleave
Abnormal inverter jumper setting
Abnormal EEPROM
Inverter radiation fin temperature rising Overheating of inverter radiation fin temperature
L4
DC output overcurrent
Inverter instantaneous overcurrent
L5
Electronic thermal
Electronic thermal switch 1
L8
Electronic thermal switch 2
Out-of-step
Speed down after startup
Lightening detection
Stall prevention (Limit time)
Stall prevention (Current increasing)
L9
Stall prevention (Defective start up)
Abnormal wave form in startup
Out-of-step
Transmission error (Between microcomputers on the outdoor main PCB)
LC
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...