Troubleshooting by Error Code
SiUS331708EA
211
Service Diagnosis
4.38 High Pressure Sensor Abnormality
Error Code
JA
Applicable
Models
All outdoor units
Method of Error
Detection
Error is detected from the pressure detected by the high pressure sensor.
Error Decision
Conditions
The high pressure sensor is short circuit or open circuit.
Pressure range: 0-4.3 MPa (0-624 psi)
Supposed
Causes
Defective high pressure sensor
Connection of low pressure sensor with wrong connection
Defective outdoor main PCB
Disconnection of high pressure sensor
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor main PCB
(A1P).
Replace the high pressure sensor
(S1NPH).
YES
NO
Replace the outdoor main PCB
(A1P).
NO
Replace the high pressure sensor
(S1NPH).
YES
YES
NO
YES
Reset the operation, and then
restart the outdoor unit.
Are the
characteristics of the
high pressure sensor
normal?
Connect to the high-pressure
sensor and then reconnect to the
power.
NO
Does
the high-
pressure sensor
connect to the corresponding
connector of the outdoor
main PCB (A1P)?
Are the characteristics of the
high pressure sensor normal? (Make a
comparison between the voltage
characteristics and the
gauge pressure.)
Is the PCB pressure detection
normal? (Make a comparison between
the checker pressure data and
the voltage
characteristics.)
CHECK 12
CHECK 12
CHECK 12
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...