Field Settings from Remote Controller
Field Settings and Test Operation
104
Swing Pattern Settings
(For units with the infrared presence/floor sensor only)
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed side by side are set
to swing in an opposite direction to agitate airflow to reduce temperature irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
Operation of Downward Flow Flap (for FXEQ-P models)
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
∗
Some indoor unit models are not equipped with draft prevention (upward) function.
Setting of the Static Pressure Selection (for FXDQ models)
CFM Table Setting (for CXTQ-TA models)
Change this setting from
Standard
to
Low
when connecting CXTQ with the following rated combinations.
Once
Low
is set, the indoor airflow CFM will be equivalent to one tonnage lower for only heat pump operation.
Note:
Change this setting only for the rated combinations of indoor units above.
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
2
01
All direction synchronized swing
02
—
03
Facing swing
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
3
01
Equipped
02
Not equipped
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
4
01
Upward (Draft prevention)
02
Standard
03
Downward (Ceiling soiling prevention)
Model No.
First Code No.
Second Code No.
Contents
13 (23)
5
01
Standard (FXDQ07-12: 10 Pa (0.04 inWG),
FXDQ18/24: 30 Pa (0.12 inWG))
02
High static pressure
(FXDQ07-12: 15 Pa (0.06 inWG),
FXDQ18/24: 45 Pa (0.18 inWG))
Combination A
Combination B
Combination C
Outdoor unit
2 ton × 1 unit
3 ton × 1 unit
4 ton × 1 unit
CXTQ
3 ton × 1 unit
4 ton × 1 unit
5 ton × 1 unit
Other indoor unit
Not applicable
Not applicable
Not applicable
Model No.
First Code No.
Second Code No.
Contents
13 (23)
5
01
Standard
02
Low
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...