Field Settings from Remote Controller
SiUS331708EA
107
Field Settings and Test Operation
Humidification when Heating Thermostat is OFF
Setting to Equipped turns ON the humidifier if suction air temperature is 20°C (68°F) or above and turns OFF the
humidifier if suction air temperature is 18°C (64.4°F) or below when the heating thermostat is OFF.
Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor fan carries out residual
operation for one minute after the thermostat is stopped. (For the purpose of preventing dust on the air filter from
falling off.)
Interlocked Operation between Humidifier and Drain Pump
This is used to interlock the humidifier with the drain pump. When water is drained out of the unit, this setting is
unnecessary.
Individual Setting of Ventilation
This is set to perform individual operation of Energy recovery ventilator using the remote controller/central unit
when Energy recovery ventilator is built in.
(Switch only when Energy recovery ventilator is built in.)
Display of Contact Center (For BRC1E73 only)
You can turn OFF the display of "DAIKIN Contact Center" as "Contact for Service Display."
Display of Error Codes on the Remote Controller (For BRC1E73 only)
Error code (four digits) is displayed for limited products.
Select two-digit display if four-digit display is not preferred.
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
1
01
Not equipped
02
Equipped
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
2
01
Not equipped
02
Equipped
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
3
01
Not interlocked
02
Interlocked
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
5
01
Not individual
02
Individual
Mode No.
First Code No.
Second Code No.
Contents
1b
3
01
Displayed
02
Not displayed
Mode No.
First Code No.
Second Code No.
Contents
1b
4
01
—
02
Two-digit display
03
—
04
Four-digit display
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...