SiUS331708EA
Outline of Control (Indoor Unit)
Functions and Control
66
Heating
When heating, the hot air rises to the top of the room, resulting in the temperature being lower near
the floor where the occupants are. When controlling by suction air thermistor only, the indoor unit
may therefore be turned off by the thermostat before the lower part of the room reaches the set
temperature. The temperature can be controlled so the lower part of the room where the occupants
are does not become cold by widening the range in which remote controller thermistor can be used
so that suction temperature is higher than the set temperature.
Assuming the set temperature in the figure above is 24°C (75°F), and the suction
temperature has changed from 18°C (64°F) to 28°C (82°F) (A
→
D):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat sensor is off.)
Suction air thermistor is used for temperatures from 18°C (64°F) to 25°C (77°F) (A
→
C).
Remote controller thermistor is used for temperatures from 25°C (77°F) to 28°C (82°F) (C
→
D).
Assuming suction temperature has changed from 28°C (82°F) to 18°C (64°F) (D
→
A):
Remote controller thermistor is used for temperatures from 28°C (82°F) to 23°C (73°F) (D
→
B).
Suction air thermistor is used for temperatures from 23°C (73°F) to 18°C (64°F) (B
→
A).
Set temperature
(Ts)
32
30
28
26
24
22
20
18
16
12 14 16 18 20 22
24 26
28 30 32 34
˚C
˚C
TH1 = Ts – 1
A B
C
D
TH1 = Ts + 1
≤
31˚C
TH1 = Ts + 12
≤
33˚C
TH1 = Ts + 10
≤
31˚C
Suction temperature (TH1)
Range in which remote controller
thermistor can be used
Range in which
suction air thermistor
can be used
Differential
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...