SiUS331708EA
Outline of Control (Indoor Unit)
Functions and Control
68
6.4.2 With Optional Infrared Presence/Floor Sensor
Whether the thermostat is turned on or off is determined by the difference between the remote
controller set temperature and the detected temperature around people.
Normal operation
· Cooling operation
· Heating operation
Dry operation
· When Tro
≤
24.5°C (76.1°F)
· When Tro > 24.5°C (76.1°F)
∗
: Description of symbols
∆
T : Room temperature or temperature around people – Remote controller set temperature
Tro : Room temperature or temperature around people at the start of dry operation
Tr : Room temperature or temperature around people
Control range of temperature around people
When the floor temperature is very low, operation using the temperature around people may cause
the suction air temperature to operate outside of use range.
To avoid the above condition, a limit based on the suction air temperature is set for the use range of
the temperature around people.
•
Cooling operation
· When the floor temperature is lower than suction air temperature (R1T), R1T will be treated as
the control target temperature for operation.
· When the temperature around people is 15°C (59°F) or lower, R1T will be treated as the
control temperature for operation.
•
Heating operation
· When the floor temperature is higher than suction air temperature (R1T), R1T will be treated
as the control target temperature in operation.
· When the temperature around people is 33°C (91.4°F) or higher, R1T will be treated as the
control temperature for operation.
Thermostat OFF
Normal operation
(Thermostat ON)
∆
T
≤
–1.0˚C (–1.8˚F)
∆
T
≥ +
1.0˚C (
+
1.8˚F)
Thermostat OFF
Normal operation
(Thermostat ON)
∆
T
≥ +
1.0˚C (
+
1.8˚F)
∆
T
≤
–1.0˚C (–1.8˚F)
Thermostat OFF
Dry operation
Tr
<
Tro – 1.0˚C (– 1.8˚F)
Tr > Tro + 1.0˚C (+ 1.8˚F)
Thermostat OFF
Dry operation
Tr
<
Tro – 1.5˚C (– 2.7˚F)
Tr > Tro + 0.5˚C (+ 0.9˚F)
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...