SiUS331708EA
Field Settings from Remote Controller
Field Settings and Test Operation
88
1. Field Settings from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of installation or after
service inspection / repair, make the local setting in accordance with the following description.
Wrong setting may cause error.
(When an optional accessory is installed on the indoor unit, settings for the indoor unit may need to be changed.)
1.1
Wired Remote Controller — BRC1E73
<Basic screen>
(1)
<Service Settings menu screen>
(2)
Press
Menu/OK
button.
<Service Settings screen>
(3)
(4)
(5)
(3)
(5)
Press
Menu/OK
button.
FIRST CODE (SW) NO.
SECOND CODE NO.
Press and hold
Cancel
button for 4 seconds or
more during backlight lit.
In the case of individual
setting per indoor unit
In the case of group total
setting
1.
Press and hold
Cancel
button for
4 seconds or more.
Service settings menu is
displayed.
2.
Select
Field Settings
in the
Service Settings menu, and
press
Menu/OK
button.
Field settings screen is
displayed.
3.
Highlight the mode, and select
desired “Mode No.” by using
(Up/Down) button.
4.
In the case of setting per indoor
unit during group control (When
Mode No. such as
20
,
21
,
22
,
23
,
25
are selected), highlight the
unit No. and select “Indoor unit
No.” to be set by using
(Up/Down) button.
(In the case of group total setting,
this operation is not needed.)
In the case of individual setting
per indoor unit, current settings
are displayed. And, SECOND
CODE NO. “ - ” means no
function.
5.
Highlight SECOND CODE NO. of
the FIRST CODE NO. to be
changed, and select desired
“SECOND CODE NO.” by using
(Up/Down) button. Multiple
identical mode number settings
are available.
In case of setting for all indoor
units in the remote control
group, available SECOND
CODE NO. is displayed as “
∗
”
which means it can be
changed.
When SECOND CODE NO. is
displayed as “ - ”, there is no
function.
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...