SiUS331708EA
Test Operation
Field Settings and Test Operation
134
2. For normal operation
Set the master unit (the indoor unit with cooling and heating option rights)
For wired remote controller
After test operation is completed, the symbol
MASTER CONTROLLED
blinks on all connected remote
controllers.
Set the master unit as per customer's request.
(It is recommended to set the indoor unit with highest frequency of use as the master unit.)
Press the operation mode changeover button on the remote controller of the master unit.
Conduct cool/heat changeover with this remote controller and the symbol
MASTER CONTROLLED
vanishes.
For other remoter controllers excluding the above, the symbol
MASTER CONTROLLED
lights up.
For wireless remote controller
After test operation is completed, timer lamps blink on all connected indoor units.
Set the master unit as per customer's request.
(It is recommended to set the indoor unit with highest frequency of use as the master unit.)
Press the operation mode changeover button on the remote controller of the master unit. Then a sound of
beeps can be heard and the timer lamps on all indoor units go out.
The indoor unit has the option rights to change between cooling/heating operation.
For details, refer to the installation manual included with the indoor unit.
After test operation is completed, operate the unit normally.
(Heating is not possible if the outdoor temperature is 24°C (75.2°F) or higher. Refer to the operation manual.)
(1) Check the indoor and outdoor units are in normal operation.
(If a knocking sound produced by liquid compression of the compressor can be heard, stop the unit
immediately.)
(2) Operate each indoor unit one by one and check the corresponding outdoor unit is also in operation.
(3) Check to see if cold (or hot) air is coming out from the indoor unit.
(4) Press the fan direction and strength buttons of the indoor unit to see if they operate properly.
About normal operation check
The compressor will not restart in about 5 minutes even if the
ON/OFF
button of the remote controller is
pressed.
When system operation is stopped by the remote controller, the outdoor unit may continue operating for
further 1 minute at maximum.
If any check operation was not performed through test operation on first installation, the error code
U3
will be
displayed. In this case, perform check operation in accordance with “1. Powering on ~ test operation”.
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...