SiUS331708EA
Field Settings from Outdoor Unit
Field Settings and Test Operation
114
2.3
Setting Mode 1
This mode is used to set and check the following items.
1. Set items ............ In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
• COOL/HEAT selection (IND) ................Used to select COOL or HEAT by individual
outdoor unit (factory setting).
• COOL/HEAT selection (MASTER) .......Used to select COOL or HEAT by outdoor unit
group with the master unit.
• COOL/HEAT selection (SLAVE)...........Used to select COOL or HEAT by outdoor unit
group with the slave unit.
2. Check items ....... The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
Procedure for changing COOL/HEAT selection setting
Press the
SET (BS2)
button to set
the blinking LED according to the
pattern shown on the right.
Press the
RETURN (BS3)
button to
determine the setting.
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Press the
RETURN (BS3)
button and
return to the initial status of setting
mode 1.
h
h
h
h
h
h
l
h
h
h
l
h
h
h
l
h
h
h
h
h
h
k
ON
h
OFF
l
Blink
Procedure for checking
Setting mode 1 is the initial status
(normal). In case of other status,
press the
MODE (BS1)
button one
time and return to the setting mode 1.
MODE
H1P
TEST
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
Low
noise
H6P
Demand
H7P
h
h
k
h
h
h
h
Setting (displaying) item
MODE
H1P
TEST
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
LOW
NOISE
H6P
DEMAND
H7P
For selection by individual outdoor
unit (factory setting)
For selection in a batch of outdoor
unit group with master unit
For selection in a batch of outdoor
unit group with slave unit
The system returns to the initial status of setting mode 1.
Current operating conditions
h
Normal
k
Abnormal
l
In preparation or in
check operation
Setting of COOL/HEAT selection
k h h
By individual outdoor
unit
h k h
In a batch of outdoor unit
group with master unit
h h k
In a batch of outdoor unit
group with slave unit
Low noise operating conditions
h
In normal operation
k
In low noise operation
Demand operating conditions
h
In normal operation
k
In demand operation
Setting mode 1 is the initial status
(normal). In case of other status,
press the
MODE (BS1)
button one
time and return to the setting mode 1.
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...