Field Settings from Outdoor Unit
SiUS331708EA
125
Field Settings and Test Operation
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P OFF)
In setting mode 2, push the
MODE (BS1)
button one time.
→
The system enters setting mode 1 and the H1P
goes off.
In setting mode 1, the H6P (In low noise operation) and the H7P (In demand control) keep lighting.
2. Setting mode 2 (H1P ON)
(1) In setting mode 1, push and hold the
MODE (BS1)
button for more than 5 seconds.
→
The system enters
setting mode 2 and the H1P lights up.
(2) Push the
SET (BS2)
button several times and match the LED display with the Setting No. you want.
(3) Push the
RETURN (BS3)
button one time, and the present setting content is displayed.
→
Push the
SET (BS2)
button several times and match the LED display with the setting content (as shown on
next page) you want.
(4) Push the
RETURN (BS3)
button two times.
→
The system returns to (1).
(5) Push the
MODE (BS1)
button one time.
→
The system returns to setting mode 1 and the H1P goes OFF.
{
: ON
z
: OFF
l
: Blink
(1)
(2)
(3)
Setting
No.
Setting
contents
Setting No. indication
Setting No. indication
Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
12
External
low noise /
demand
setting
{
z
z
z
z
z
z
{
z
z
{
{
z
z
NO
(Factory
setting)
{
z
z
z
z
z
l
YES
{
z
z
z
z
l
z
22
Night-time
low noise
setting
{
z
{
z
{
{
z
OFF
(Factory
setting)
{
z
z
z
z
z
z
Level 1
{
z
z
z
z
z
l
Level 2
{
z
z
z
z
l
z
Level 3
{
z
z
z
z
l
l
26
Night-time
low noise
operation
start setting
{
z
{
{
z
{
z
08:00 PM
{
z
z
z
z
z
l
10:00 PM
(Factory
setting)
{
z
z
z
z
l
z
12:00 AM
{
z
z
z
l
z
z
27
Night-time
low noise
operation
end setting
{
z
{
{
z
{
{
06:00 AM
{
z
z
z
z
z
l
07:00 AM
{
z
z
z
z
l
z
08:00 AM
(Factory
setting)
{
z
z
z
l
z
z
29
Capacity
precedence
setting
{
z
{
{
{
z
{
Low noise
precedence
(Factory
setting)
{
z
z
z
z
z
l
Capacity
precedence
{
z
z
z
z
l
z
30
Demand
setting 1
{
z
{
{
{
{
z
60% of
rated power
consumption
{
z
z
z
z
z
l
70% of
rated power
consumption
(Factory
setting)
{
z
z
z
z
l
z
80% of
rated power
consumption
{
z
z
z
l
z
z
32
Constant
demand
setting
{
{
z
z
z
z
z
OFF
(Factory
setting)
{
z
z
z
z
z
l
ON
{
z
z
z
z
l
z
Setting mode indication section
Setting No. indication section
Set contents indication section
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...