15. Enviroment setting■
◆DC Bus & current fine tune
Description: This function is to adjust the calibration of voltage positioning on DC BUS between detected
and actual position. The display value is higher when set at bigger figure.
Cd67: 220V series, when setting value > 15V equal to 15V。
400V series, can set up to 30V.
◆Motor specification
Description: CE82 86 : The motor values are shown after execute autotuning.
( CE82 85for FG –Type only)
CE87 : Inverter load specification of inverter (FG –Type only)
1: 150% overload (heavy load model)
2: 120% overload (light load moodel)
◆Data lock
Information:Data lock to prevent unperfesional operator to input unsuitable data.
Cd98=0 Read only mode: Data lock, but operation frequency could be input by numeric keys or
incresement , decresment keys.
Cd98=1 Simple mode: Some constants could be read and modified.
Cd98=2 Macrocosm mode: All constants could be read and modified.
Constant No.
Constant name
Settable range
Factory setting
Change during
operation
Cd67
DC Bus fine tune
± 30.0V
0.0V
X
CE98 Current
display fine tune value
± 100.0%
0.0
X
Constant No.
Constant name
Settable range
Factory setting
Change during
operation
CE82 Motor
slip
0.00 20.00
2.00HZ
X
CE83
Motor Noload current
10.0 100.0
30.0%
X
CE84
Motor pole
2 8
4 pole
X
CE85
Motor leakage inductance
0.0 40.0
0%
X
CE86
Motor resistance (RS)
0.000 65.000
By specification
X
CE87
Select
load 0 1 1 X
Constant No.
Constant name
Settable range
Factory setting
Change during
operation
Cd98 Data
lock
0 2 2 X