50
◆Multi-functions analog input functions list
Constant No.
Name Description
0 De-active
---
1
Analog master speed (1
st
step spped)
Frequency command 1
2
Adding master speed
Analog master speed auxiliarycommand
3
Master spped gain
Analog master speed limit gain
4
Auxiliary frequency 2 (2
nd
step spped)
frequency command 2
5
Auxiliary frequency 3 (3
rd
step spped)
frequency command 3
6
DC braking current
Inverter rated current
7
PID feedback value
Feedback value source
8
PID command value
PID input value
◆Analog output setting
Description: Multi-function analog output can be selected monitoring (d1-xx) to transfer to analog voltage
output, when selected one is 100%, output 10V. Please refer to d1 constants, page 38.
The function of Cd87 could be set as the filter time of VOUT. The filter time setting is longer, the capability
of reject fiter is stronger, but the reaction of input become slow. Please set the adaptable time by user request.
Cd88、Cd90 can be set analog output bias (output is lower than 0V, output 0V only).
Cd89、Cd91 can be set analog output enlarge magnification (output exceed 10V, output 10V only).
9. Output/ input terminals ■
Constant
No.
Constant name
Settable range
Factory setting
Change during
operation
Cd87
Analog filter time
50 1000
100
O
Cd88
Analog output 1(FM) bias
±10.0
0.0%
O
Cd89
Analog output 1(FM) gain
0.00 2.50
1.00
O
Cd90
Analog output 2(AM) bias
±10.0
0.0%
O
Cd91
Analog output 2(AM) gain
0.00 2.50
1.00
O