6. Constant tables
■
Constant
NO
Name
Description
Setting
value
Factory
setting
Change
during
operation
Com.
add.
Page
Cd-59
Unload current
adjusting (FG
only)
Increase the values when unload current is bigger,
Decrease the values when it is lower. Collocate
Cd-60 to adjust.
30
150
60% No X P61
Cd-60
Torque bosst
frequency (FG
only)
Set torque boost operation frequency
1.5 10
2.50
HZ
No X
P61
Cd-61
Selecting PWN
frequency
Select fixed PWM frequency:
0: 2k 1: 3k 2: 3.5k 3: 4k 4: 5k 5: 6k
6: 7k 7: 8k 8 15: 4k
15: Set by Cd62 and Cd63
0 15 2 No 189
P88
Cd-62
Maximum PWM
frequency setting
Settable PWM maximum frequency freely
(operation frequency will be higher)
2.0 8k
6k No 190
P88
Cd-63
Minimum PWM
frequency setting
Settable PWM minimum frequency freely (operation
frequency will be lower)
2.0 8k
3k No 191
P88
Cd-64
Dynamic braking
mode
Set brake mode
0: operation wnen run
1: no operation when speed is the same
0 1 1 No 192
P87
Cd-65
Dynamic braking
voltage
positioning
Set 20V equal to 350+20=370Vdc DB on
0 40V
20V
No
198
P87
Cd-66
Instantinitial
field time
Instantinitial field time when start motor.
00 20.0
0
0.06S No 193
P89
Cd-67
Fine tune
DC Bus standard
score
Adjust the standard score of DC Bus
± 15.0V 0V
No
195 P90
Cd-68
Stall preventive
function in accel.
0: Invalid
1: Valid
0 1 1 No 535 P79
Cd-69
Stall preventive
level in accel.
Set rated current as 100% for stall preventive
leveling acceleration
30 200 125% No 536 P79
Cd-70
Stall prevention
limit during
accleration
In accordance with Cd70 setting value when inverter
operation is over motor rated frequency to reduce
stall prevention limit during accleration
30 100 50% No 537 P80
Cd-71
Stall prevention
limit during
deceleration
0: Invalid
1: Valid
0 1 1 No 538 P81
Cd-72
Over current
voltage active
point
Over voltage protection function active point
(20V=355+20=375Vdc)
0 50 20 No 199 P81
Cd-73
Constant speed
stall prevention
during operation
: Decelerate by deceleration time 2 (Cd12)
0 1
1
No
539 P82
Cd-74
Constant speed
stall preventive
level during
operation
Set rated current as 100% for constant speed stall
preventive level
30 200 125% No 540 P82