44
◆Frequency command selecting
Constant No.
Constant name
Settable range
Factory setting
Change during
operation
Cd01 Selecting
frequency command
0 7
0
X
Description: Constant Cd01 is input way selecting of frequency, selectable items as following:
0: Digital input by key board
1: Analog input
2: Analog input (lag)
3: Multi-step function 1
4: DI UP/DOMN(2)
5: Pulse input (option)
6: Keypad UP/ DOMN (1)
7: Keypad UP/ DOMN (2)
■ Use keypad to input frequency command
Input frequency command by keypad after set Cd01=0. Use constant Cd00 to input frequency commad when
ordinary operation.
■ Use voltage (current) to input frequency command (analog input IN1 IN3, option cardAI1 2)
Input frequency command by analog input after set Cd01=1.
Input frequency command (contained lag) by analog input after set Cd01=2.
■ Input frequency command by multi-step function to set multi-step function
Set Cd01=3 to execute multi-step function. 16 steps are settable and set each step command by CE05 CE36.
(Please refer to page 67)
■ DI UP/ DOMN
Set DI terminal to execute frequency UP/ DOMN by Cd92 Cd97 after set Cd01= 4.
Set acceleration/ deceleration by Cd10.
(Please refer to page P51)
■ Pulse input (option card is underdevelopment)
Use pulse input terminal of option card to input pulse as frequency after set Cd01=5.
■ Keypad UP/DOMN
Set frequency by ▲、▼ UP/ DOMN of keypad after set Cd01= 6, 7.
Set acceleration/ deceleration by Cd10.
8. Constant setting by function
■